THIS FIELD NOTICE IS PROVIDED ON AN "AS IS" BASIS AND DOES NOT IMPLY ANY KIND OF GUARANTEE OR WARRANTY, INCLUDING THE WARRANTY OF MERCHANTABILITY. YOUR USE OF THE INFORMATION ON THE FIELD NOTICE OR MATERIALS LINKED FROM THE FIELD NOTICE IS AT YOUR OWN RISK. CISCO RESERVES THE RIGHT TO CHANGE OR UPDATE THIS FIELD NOTICE AT ANY TIME.
Revision | Publish Date | Comments |
---|---|---|
1.0 |
22-Dec-16 |
Initial Release |
10.0 |
09-Oct-17 |
Migration to new field notice system |
10.1 |
29-Nov-17 |
Updated Umpire Dates |
10.2 |
19-Jan-18 |
Minor Edit - Changed wordings in Workaround/Solution section |
10.3 |
02-Mar-18 |
Updating the replacement PID in the Umpire Order Form |
10.4 |
24-May-21 |
Updated the Workaround/Solution Section and Removed the Upgrade Program Section |
Affected Product ID | Comments |
---|---|
N55-PAC-1100W |
|
N55-PAC-1100W-B |
Defect ID | Headline |
---|---|
CSCuf57615 | Nexus 5596UP/600x: Silent reload with i2code cause 0x0800 or 0x2 |
A particular component failure in N55-PAC-1100W and N55-PAC-1100W-B power supply units (PSUs) can cause the entire 5596UP or Nexus 600x switch to reload.
All N55-PAC-1100W power supplies with a Part Number 341-0415-01 or 341-0415-02 are impacted. N55-PAC-1100W power supply with Part Number 341-0415-03 are not impacted.
All N55-PAC-1100W-B power supplies with a Part Number 341-0461-01 or 341-0461-02 are impacted. N55-PAC-1100W-B power supply with Part Number 341-0461-03 are not impacted.
Note: The previously published impacted Serial Number (S/N) range of "POG1746XXXX and below" still applies if the power supply Part Number is not 341-0415-03 or 341-0461-03. However, it is recommended that impacted PSUs be identified by Part Number instead of S/N, as detailed in the preceding paragraphs.
The most common reason for the system reset is loss of power to the switch. Make sure the switch has dual power supplies connected to different power distribution units (PDUs) and power to the switch is stable.
This bug is seen on switches with redundant power supplies powered up and when one of the power supplies goes bad, which triggers the entire switch to reload.
A single PSU failure in a Nexus 5596UP or Nexus 600x switch might cause the entire system to reboot.
If the Nexus 5596UP or Nexus 600x switch shows the problem mentioned in the Problem Symptom section and the power supply Part Number of the switch as mentioned in the Problem Description section, request a replacement of the power supply unit.
See the How to Identify Affected Products section for instructions on how to view the version of in-service product.
To identify the affected products, please run the below commands and check for the Power Supply Part Number as mentioned in the Problem Description section.
5596B# show sprom powersupply 2 | egrep Product|Part|Serial Product Number : N55-PAC-1100W Serial Number : POG151350GJ Part Number : 341-0415-01 Part Revision : B0 5596B#
If you require further assistance, or if you have any further questions regarding this field notice, please contact the Cisco Systems Technical Assistance Center (TAC) by one of the following methods: